Analogue transmitter installationA transmitter is calibrated to a specific measurement range. The measurement range is shown on the calibration label on the transmitter. Normally calibration is stated as: “Minimum measurement value” to “Maximum measurement value”.
The analogue input module converts the transmitter signal (0-20mA / 4-20mA / 0-100mV) to a real process value in SI engineering units, based on ZeroPoint and Span.
Direct transmitter signal:If the transmitter measures the absolute process value, the installation is very simple: ZeroPoint is loaded with the Minimum measurement value. Span is loaded with the difference between the Maximum and
Minimum measurement range. (Maximum – Minimum).
Scaled transmitter signal:If the transmitter does not measure the absolute process variable, the data from the label cannot be used directly, e.g. a tank content, measured by a pressure transmitter adjusted to a certain water column of X meters. In this case, the tank content depends on the tank diameter, bottom cone shape, density of the product etc. ZeroPoint and Span must therefore be adjusted to reflect the real process variable. This is achieved in three steps:
Raw transmitter signal:If the transmitter signal is to be used in a calculation that cannot be performed by the analogue module, e.g. a non-linear system, one of the following set-ups can be used.
To read out the raw signal in mA or mV the following constants must be used:
To read out the signal in %, use the following constant: (Same constant for all signal types)
Example 1:A pH transmitter is calibrated to measure 4pH to 9pH. ZeroPoint is set to 4 and Span is set to 5.
Example 2:Tank contents measurement with a pressure transmitter adjusted to x meter of water column, is used as a tank contents transmitter: Installation and adjustment:
Related TopicsAnalogIn calculation principle Transmitter error compensation PD 642 Application Notes (mV / thermocouple)
|