550 770 01

 

4-WIRE P-NET Cable:

 

4-WIRE P-NET specifies the use of a shielded cable having 2 individual twisted pairs.

The communication pair must have a characteristic impedance of 100 to 120Ω and a minimum core cross-section of 0.22mm² / 24 AWG.  To ensure maximum signal integrity over long bus cables, it is recommended that the core cross-section of the communication pair be increased.

 

Bus length:

Recommended core cross section (communication pair):

 

0 – 100m

Minimum 0.22 mm²  /24 AWG

 

100m – 400m.

Minimum 0.34 mm²  /22 AWG

 

400m – 600m.

Minimum 0.50 mm²  /20 AWG

 

 

The size of the power pair should be calculated in consideration of maximum current, voltage drop, cable resistance, bus length etc.

 

 

 

Cable, recommended for 4-WIRE P-NET:

 

Cable for 4-WIRE P-NET must be carefully selected to ensure stable communication as well as for providing sufficient power for all devices.

 

 

 

Resistance in wire:

mm²

AWG

 Ω / km.

0.21

24

88

0.25

 

72

0.34

22

52

0.5

 

34

0.52

20

34

0.75

 

23

0.82

18

22

1.0

 

18

1.31

16

13

1.5

 

11

1.68

15

10.4

2.08

14

8.5

2.5

 

7

2.6

13

6.7

 

 

The values in the above table are only intended as a guide; wire cross section area and resistance vary by cupper alloy, number of stranding etc.

 

 