PD 990 4-WIRE P-NET Conditioner
The PD
990 4-WIRE P-NET Conditioner unit is a multipurpose device that is used
for:
- Termination of a 4-WIRE
P-NET bus.
- Connection of a traditional
P-NET module to a 4-WIRE
P-NET bus.
- Connection and termination
of a traditional P-NET module to a 4-WIRE P-NET bus.
The PD
990 4-WIRE P-NET Conditioner is delivered as a moulded unit with 5 wires of 200 mm
length.
|
|
|
PD 990 4-WIRE P-NET Conditioner Block Schematic
Power
supply
|
Power
supply DC:
|
Nom
|
24.0 V
|
min.
|
18.0 V
|
max.
|
32.0 V
|
Ripple
voltage:
|
max.
|
5 %
|
|
|
|
Power consumption @ 24V DC
|
|
|
Operation:
|
max.
|
20 mA
|
Current at power up:
|
max.
|
25mA
|
|
|
Ambient
temperature range
|
Operating
temperature:
|
-25 °C
– 70 °C
|
|
Storage
temperature:
|
-40 °C
– 85 °C
|
|
|
Humidity
|
Relative
humidity:
|
max.
|
95 %
|
|
EMC
|
Immunity:
|
EN 61000-6-2
|
Emission:
|
EN 50082-1
|
|
Vibration
|
Test
method:
|
IEC
60068-2-6
|
Frequency
/ amplitude:
|
2-10
Hz: +/- 5.0 mm
|
10-100
Hz: +/- 2g
|
Sweep
rate:
|
max. 1
octave/min
|
Number
of axes:
|
3 mutually
perpendicular
|
|
|
|
|
Mechanical details:
Related topics
Installation guide PD 990 4-WIRE P-NET
Conditioner
Installation guide 4-WIRE P-NET topology
Overview PD 66x communication devices
|