Notification on analogue channelsNotification is a means of raising a flag when a selectable event occurs.
Notification on analogue channels can be selected as
Notification on limit crossing can be enabled to create a flag when the AnalogIn value crosses the defined limits while increasing and/or decreasing. Two limits can be defined per channel: Level1 and Level2.
Notification on DeltaLevel can be enabled to create a flag, when the AnalogIn value has changed by more than a certain level. DeltaLevel defines by how much a measured value needs to change either positively or negatively (deviate), compared to the last DeltaLevel Notification value, for a new notification to be made.
No load / Wire broken, when using the analogue channels in 4–20 mA mode, a current monitor can be enabled to make a notification if the current drops below 3 mA.