| Notification on analogue channelsNotification is a means of raising a flag when a selectable event occurs. 
 Notification on analogue channels can be selected as 
 
 
 Notification on limit crossing can be enabled to create a flag when the AnalogIn value crosses the defined limits while increasing and/or decreasing. Two limits can be defined per channel: Level1 and Level2. 
 
 
 
 Notification on DeltaLevel can be enabled to create a flag, when the AnalogIn value has changed by more than a certain level. DeltaLevel defines by how much a measured
  value needs to change either positively or negatively (deviate), compared to
  the last DeltaLevel Notification value, for a new notification to be made.  
 No load / Wire broken, when using the analogue channels in 4–20 mA mode, a current monitor can be enabled to make a notification if the current drops below 3 mA.
 (See also: ChConfig.EnableNotification) 