| All input channel signal levels are
  constantly monitored. If the signal is outside the specified limits, an alarm
  will be generated.     (See also: ChError.)   
   
    | Signal too high:     | Alarm bit “SignalHigh” is set if the
    input signal exceeds 20 mA by more than 10%. (22 mA) (AnalogIn is held at
    22 mA) |  
    | Signal too low:     | Alarm bit “SignalLow” is set if the
    input signal falls below 0 mA by more than 5%. (-1 mA) (AnalogIn is held at
    –1 mA) |  
    | No load /  Wire broken:     | 4-20 mA mode only: A monitor of the
    input signal can be enabled to create an alarm “NoLoad” if the current
    falls below 3 mA.  This will indicate a no load or wire
    broken situation. |      
   
    | Signal too high:     | Alarm bit “SignalHigh” is set if the
    input signal exceeds 200 °C. (AnalogIn is held at 200 °C) |  
    | Signal too low:     | Alarm bit “SignalLow” is set if the
    input signal falls below –100 °C. (AnalogIn is held at -100 °C) |      
   
    | Signal too high:     | Alarm bit “SignalHigh” is set if the
    input signal exceeds 100 mV by more than 10%, (110 mV) (AnalogIn is held at
    110 mV), or exceeds the thermocouple’s specified range: Type E: +1000 C Type K: +1372 C Type N: +1300 C Type R: +1768 C Type S: +1768 C Type T: +400 C Type J: +1200 C Type B: +1820 C (AnalogIn is held at high limit)   |  
    | Signal too low:     | Alarm bit “SignalLow” is set if the
    input signal falls below 0 mV by more than 5%, (-5 mV) (AnalogIn is held at
    110 mV), or falls below the thermocouple’s specified range: Type E: -94.8 C Type K: -53.7 C Type N: -270 C Type R: -50 C Type S: -50 C Type T: -166.5 C Type J: -109.1 C Type B: 0 C. (AnalogIn is held at low limit) |      Notification Limit
  alarms Transmitter
  installation AnalogIn
  calculation principle Signal
  filter Application
  note for PD 640 (mA) Application
  note for PD 641 / 643 (Pt100 / Pt 1000)      Application
  note for PD 642 / 643 (mV / thermocouple)  Analogue modules     |