Level alarms on analogue channels

 

Alarms on analogue channels can be selected as

  • AnalogIn higher than Level1
  • AnalogIn higher than Level2
  • AnalogIn lower than Level1
  • AnalogIn lower than Level2.
  • No load / Wire broken.

 

Limit alarm can be enabled to create an alarm signal, when the AnalogIn values are higher and/or lower than the limits specified. Level1 and Level2 alarm conditions can be combined freely, which makes the system very flexible.

 

No load / Wire broken. When using the analogue channels in 4–20 mA mode, a current monitor can be enabled to produce an alarm if the current drops below 3 mA.

 

(See also: ChConfig.EnableFunctions)

 

Example 1:

 Alarm used for monitoring “Signal too high” or “Signal too low”:

 

 

 

 

 

Example 2:

Alarm used for monitoring “Signal high” or “Signal too high”

 

 

Related Topics

Notification

Signal out of range alarms

Application note for PD 640 (mA)

Application note for PD 641 / 643 (Pt100 / Pt 1000)    

Application note for PD 642 / 643 (mV / thermocouple)

Analogue modules