| Level alarms on analogue channels
 Alarms on analogue channels can be selected as 
 
 Limit alarm can be enabled to create an alarm signal, when the AnalogIn values are higher and/or lower than the limits specified. Level1 and Level2 alarm conditions can be combined freely, which makes the system very flexible. 
 No load / Wire broken. When using the analogue channels in 4–20 mA mode, a current monitor can be enabled to produce an alarm if the current drops below 3 mA.
 (See also: ChConfig.EnableFunctions) 
 Example 1:Alarm used for monitoring “Signal too high” or “Signal too low”: 
 
 
 
 
 
 Example 2:Alarm used for monitoring “Signal high” or “Signal too high” 
 