550 765 01

 

 

 

 

P-NET Bus Topology:

 

 

 

 

With P-NET bus topology; both ends of the network must be terminated.

 

The two nodes at the ends must be BM 010 base module configured for termination.

When used as termination module the P-NET #1 must be connected to the 1'st terminal column from the left (terminals: 1,5,9).

 

All nodes between the two termination nodes are connected in the same way as modules in P-NET ring topology.  BM 010 base modules used apart from the ending modules must be configured for loop through.

 

P-NET installed as bus topology can have a maximum length of 600 metres and can contain up to 125 devices.

 

 

 

Wiring topics:

P-NET wiring

P-NET cable

P-NET shield connection

 

 

 

 

 

 

Related topics:

Installation overview